Column Reinforcement Requirement
There are two
kinds of reinforcement in a column; Longitudinal and transverse reinforcement.
The purpose of transverse reinforcement is to hold the vertical bars in a
position providing lateral support so that individual bars cannot buckle
outwards and split the concrete. Transverse reinforcement does not contribute
to the strength of a column. Below are the requirements that must be satisfied
in the reinforcement concrete column per code.
1. The
minimum area of cross section of longitudinal bars must be at least 0.8% of the
gross sectional area of the column.
2.
The
maximum area of cross section of longitudinal bars must not exceed 6% of the
gross sectional area of the column.
3.
In
any column that has a larger cross sectional area than that required to support
the load, the minimum percentage steel must be based on the area of concrete
required to resist the direct stress and not on the actual area.
4.
The
bar should not be less than 12 mm in diameter so that it is sufficiently rigid
to stand up straight in the column forms during fixing and concreting.
5.
The
minimum number of longitudinal bars must be 4 in rectangular column and 6
in circular column.
6.
A
reinforced concrete column having helical reinforcement must have at least 6 bars of longitudinal reinforcement
within the helical reinforcement and must be in contact with helical
reinforcement. Also equidistant around its inner circumference.
7.
Spacing
of longitudinal bars measured along the periphery of a column should not exceed
300 mm.
8.
In
case of pedestals, in which the longitudinal reinforcement is not taken into
account in strength calculations, nominal longitudinal reinforcement should not
be less than 0.15% of the cross sectional area. A pedestal is a compression member
whose effective height does not exceed three times the least lateral dimension.
![]() |
Comments
Post a Comment